Can you tie these lights straight to a 110 volt 20amp circuit? Actually I would like to get 5 of these 175 watt metal halide cut off flood lights.  I have two 20amp circuits to my poles one circuit has 3 lights and the other has 2 lights. 12 gauge wire ran to lights.

  Add to Favorites

re: Techlight - Cut Off 175watt HID Flood DCMB1DL1

Posted: 9/24/2006 10:07:11 PM

EXPERT

9/24/2006 10:07:11 PM
Sure, these 175 watt metal halide floods only pull 1.2 amps each.  You should have no problem adding 8-10 lights on a 20 amp circuit.  You may want to get a Tork time clock to control them.